What fire and life-safety inspections can your own staff perform?

Most facilities pay contractors for tasks their own trained staff can legally perform and document. Here is every task, tiered by who may perform it under the national codes — and marked honestly where your local jurisdiction is likely to say otherwise.

The question sounds like it should have a simple answer. It doesn't, because two different rulebooks apply at once. The national consensus standards — NFPA 72 for fire alarm, NFPA 25 for sprinklers, NFPA 10 for extinguishers, NFPA 80 for fire doors, NFPA 101 for egress lighting, NFPA 110 for generators — mostly require a qualified person, which they define by training and competence rather than by license. Then state licensing law and your local fire marshal layer on top, and they frequently do require a licensed contractor for specific tasks. Most guidance you'll find online picks one of those two rulebooks and pretends the other doesn't exist.

So this page does something different: it states the national baseline task by task, and it puts a on every task where the local answer commonly differs — instead of guessing. Those starred tasks are exactly where the money is, and exactly where a wrong assumption gets you cited. The honest move is to ask your AHJ directly, which is why the calendar builder prints those questions as a sheet you can take to them.

Tier 1 — any trained staff member

These need orientation, not credentials. They are also the most frequent tasks on any calendar, which is why they dominate the savings math: a contractor billing a monthly visit adds up far faster than one annual test. Every one of these produces a log entry that is itself the compliance record.

TaskSystemFrequencyCode (edition)What qualifies your person
Panel visual — trouble/supervisory indicators, power, ground faultsFire alarmMonthlyNFPA 72 §14.3 (visual inspection) (2022)Any competent staff member after orientation.
Pull stations & notification appliances unobstructed, undamaged, in placeFire alarmMonthlyNFPA 72 §14.3 (2022)In-house walk-through.
Gauges + control valves (dry / pre-action / deluge)Sprinkler systemWeeklyNFPA 25 Table 5.1.1.2 (2023)In-house with training; dry systems require weekly gauge checks.
Gauges + alarm valves (wet systems)Sprinkler systemMonthlyNFPA 25 Table 5.1.1.2 (2023)In-house with training.
Control valves: sealed / locked / supervised, correct positionSprinkler systemMonthlyNFPA 25 §13.3 (2023)In-house. Closed control valves cause the majority of sprinkler activation failures.
Portable extinguisher visual — access, gauge, seal, condition, in placeFire extinguishersMonthlyNFPA 10 §7.2 (monthly inspection) (2022)In-house; tag/log kept at least 12 months.
Fire door visual — not propped, unobstructed, undamaged, labels visibleFire doorsMonthlyNFPA 80 §5.2 (periodic) (2022)In-house walk; supports the annual inspection.
Emergency lighting — 30-second functional testEmergency / exit lightingMonthlyNFPA 101 §7.9.3 (monthly 30-sec) (2021)Fully in-house under the national code.
Exit sign illumination checkEmergency / exit lightingMonthlyNFPA 101 §7.10 (2021)In-house, part of the monthly walk.
Grease filter cleaning / swapCommercial kitchen hoodWeeklyNFPA 96 §12.1 (2024)In-house; frequency by cooking volume.
Machine room housekeeping / visualElevator(s)MonthlyASME A17.1 §8.6 (2019)In-house — keep the machine room clean and clear.
Backflow preventer visual — leaks, damageBackflow preventer(s)MonthlyBest practice / ASSE 5013In-house visual.
Filter inspection / replacementHVACMonthlyASHRAE/ACCA 180 §5 (2018)In-house.
Eyewash / shower — weekly activation & flush of dead-leg water; confirm flushing fluidEyewash stationsWeeklyANSI/ISEA Z358.1-2014 §7.5.2 (2014)No certification prerequisite under the standard — competent-person training (manufacturer or online) is sufficient. In-house eligible.
Water heater T&P valve test & visualWater heater(s)AnnualManufacturer / best practice (verify)In-house best practice (verify against equipment/manufacturer).
Damper access panels unobstructed; no visible damage or blocked linkageFire / smoke dampersAnnualNFPA 80 §19.4 (access) (2022)In-house staff during rounds.
Firefighters emergency operation — Phase I recall and Phase II in-car testElevator(s)MonthlyASME A17.1 §8.6.11.1 (2019)In-house staff may run the monthly test; record results.
Private fire hydrant inspection — caps, threads, drainage, obstructionPrivate fire hydrantsAnnualNFPA 25 §7.2.2 (hydrant inspection) (2020)In-house staff may inspect; flow test is contracted.
Tank water level, temperature and heating system checkFire water storage tankMonthlyNFPA 25 Table 9.1.1.2 (2020)In-house staff.
Nurse call system test — every station, pull cord and dome lightNurse call systemMonthlyIndustry practice (senior-living task library)In-house; log by room.
Door monitors and wander-management system checkWander management / elopementWeeklyIndustry practice (senior-living task library)In-house; verify each exit and each transmitter.
Bed rail inspection — entrapment zones, latches, hardwareElectric beds & railsMonthlyFDA Hospital Bed Safety Workgroup guidanceIn-house.
Resident lift inspection — sling, straps, battery, emergency loweringResident liftsMonthlyIndustry practice (senior-living task library)In-house; remove from service on any sling wear.
Resident scale calibration checkResident scalesMonthlyIndustry practice (senior-living task library)In-house with test weights.
Wheelchair and walker inspection — brakes, tyres, footrestsWheelchairs & mobility aidsMonthlyIndustry practice (senior-living task library)In-house.
Oxygen concentrator check — filters, flow, alarmsOxygen concentratorsMonthlyIndustry practice (senior-living task library)In-house per manufacturer.
AED check — pad expiry, battery indicator, unit present and accessibleDefibrillators (AED)MonthlyIndustry practice (senior-living task library)In-house; a missing or expired pad is a survey finding.
Water management control-point monitoring — temperature and disinfectant residualWater management (Legionella)WeeklyASHRAE 188 §7 (2018)In-house once control limits are set.
Hot water temperature test and log at resident fixtures (scald prevention)Water management (Legionella)WeeklyIndustry practice (senior-living task library)In-house; log location, temperature and time.
Water hardness testWater management (Legionella)MonthlyIndustry practice (senior-living task library)In-house.
Dryer vent and lint duct cleaning — full run, not just the trapDryer vents & lint ductsWeeklyIndustry practice (senior-living task library)In-house; lint accumulation is a leading laundry fire cause.
Grease trap inspectionGrease trapsMonthlyIndustry practice (senior-living task library)In-house.
Power cord and extension cord inspection — no daisy-chains, no damageElectrical distributionMonthlyNFPA 99 §6.3 / OSHA 1910.305In-house during rounds.
Corridor door check — latching, no impediments, no unapproved hold-opensEgress, corridors & smoke barriersMonthlyNFPA 101 §19.3.6 (2012)In-house.
Smoke barrier and fire wall inspection — penetrations, above ceilingEgress, corridors & smoke barriersMonthlyNFPA 101 §19.3.7 (2012)Unsealed penetrations are a top survey citation.
Hazardous area door check — self-closing and latchingEgress, corridors & smoke barriersMonthlyNFPA 101 §19.3.2 (2012)In-house.
Decoration and corridor projection check — flame spread and clearanceEgress, corridors & smoke barriersMonthlyNFPA 101 §19.7.5 (2012)In-house; seasonal decorations drive citations.
Safety committee meeting with minutesSafety & OSHA programMonthlyIndustry practice (senior-living task library)Minutes are the evidence.
Dishwasher check — wash and rinse temperatures, sanitiser concentrationKitchen equipment & refrigerationMonthlyFDA Food Code §4-501.112 / §4-501.114 (as adopted by your state) (2022)In-house; health-department evidence.
Ice machine — filters, coils, sanitise interior, delimeKitchen equipment & refrigerationQuarterlyIndustry practice (senior-living task library)In-house or vendor.
Refrigerator and freezer temperature logKitchen equipment & refrigerationWeeklyFDA Food Code §3-501.16 (cold holding, as adopted by your state) (2022)In-house; a health-department staple.
Refrigeration condenser coil cleaningKitchen equipment & refrigerationSemi-annualIndustry practice (senior-living task library)In-house.
Carbon monoxide detector testFire alarmMonthlyNFPA 72 §17.12 (CO detection; NFPA 720 withdrawn 2018) + state CO law (2022)In-house.
Carbon monoxide and battery smoke detector battery changeFire alarmSemi-annualIndustry practice (senior-living task library)In-house.
Exhaust fan operation check and cleaningHVACMonthlyIndustry practice (senior-living task library)In-house.
Air temperature test and log in resident areasHVACWeeklyIndustry practice (senior-living task library)In-house.
Facility vehicle safety inspection — lights, brakes, tyres, liftFacility vehiclesMonthlyIndustry practice (senior-living task library)In-house.

Tier 2 — a designated qualified person

Still in-house, but the standard expects documented training on the specific task, and the person's name and qualification go on the record. This is the tier facilities most often forfeit unnecessarily — a maintenance tech trained on the generator can run the monthly load test and produce a better record than a contractor who visits once, because they are there when it matters.

TaskSystemFrequencyCode (edition)What qualifies your person
Component visual inspections per Table 14.3.1Fire alarmSemi-annualNFPA 72 Table 14.3.1 (2022)Trained, qualified person; name & qualification on the record.
CO detector replacementFire alarmEvery 5 yearsNFPA 72 §17.7 / manufacturer (2022)Per manufacturer end-of-life; staff-replaceable units.
Fire pump churn test — diesel weekly / electric monthly (no-flow, 10 min)Fire pumpWeeklyNFPA 25 §8.3.1 (2023)Trained staff run the churn test; record load, duration, and transfer.
90-minute full battery discharge testEmergency / exit lightingAnnualNFPA 101 §7.9.3 (annual 90-min) (2021)In-house with training; log the full 90-minute run.
EPSS inspection — fuel, oil, coolant, batteries, charger, leaksEmergency generatorWeeklyNFPA 110 §8.4.1 (weekly inspection) (2022)Trained staff checklist.
Exercise under load — ≥30 min, ≥30% nameplate (diesel)Emergency generatorMonthlyNFPA 110 §8.4.2 (monthly load run) (2022)Trained staff run the monthly load test; record load, duration, transfer.
Starting battery replacement (per manufacturer)Emergency generatorEvery 2 yearsNFPA 110 §8.3.7 / manufacturer (2022)Staff-replaceable; ~2–3 years per manufacturer.
Coil cleaning, condensate, beltsHVACQuarterlyASHRAE/ACCA 180 §5 (2018)Trained maintenance staff.
Eyewash / shower — annual full inspection (flow, temperature, condition)Eyewash stationsAnnualANSI/ISEA Z358.1-2014 §7.5.5 (2014)Competent-person training sufficient; many facilities use third-party annuals for credibility. In-house eligible.
Pool / spa inspection & water testing (state/local health code)Pool / spaMonthlyState/local pool health code (verify)Per state/local health code — verify frequency.
Roof inspection — semi-annual + after major stormsRoofSemi-annualIndustry standard (verify insurer requirement)Industry standard / insurer-driven, not code-fixed.
Hydrostatic test — dry chemical, CO2, halon (12-year cycle)Fire extinguishersEvery 12 yearsNFPA 10 Table 8.3.1 (12-yr agents) (2022)Licensed extinguisher service company.
Sprinkler head sample test — fast-response heads (20 years, then every 10)Sprinkler systemEvery 20 yearsNFPA 25 §5.3.1.1.1.2 (2020)Licensed sprinkler contractor; sample sent to a testing laboratory.
Dry-pipe valve partial trip test (priming water, low-point drains)Sprinkler systemAnnualNFPA 25 §13.4.4.2.1 (annual partial trip) (2020)Licensed sprinkler contractor.
Antifreeze solution test — specific gravity / freeze point at each loopSprinkler systemAnnualNFPA 25 §5.3.4 (antifreeze) (2020)Licensed sprinkler contractor; solution must be listed.
Private fire hydrant flow testPrivate fire hydrantsEvery 5 yearsNFPA 25 §7.3.2 (5-year flow test) (2020)Licensed contractor or fire department.
Fire drill — weekend shift (retain signed sheet)Fire drills (by shift)QuarterlyIndustry practice (senior-living task library)Facility staff.
Second exercise of choice (tabletop, workshop, or drill)Emergency preparedness drillsAnnual42 CFR §483.73(d)(2)Paired with the full-scale exercise.
Grease trap pumped by contractorGrease trapsSemi-annualLocal sewer authorityLicensed waste hauler; keep the manifest.
Main and feeder circuit breaker inspection, documentedElectrical distributionAnnualNFPA 70B (Standard — mandatory language since the 2023 edition) (2023)Qualified electrician.
Smoke door assembly inspectionEgress, corridors & smoke barriersAnnualNFPA 105 Ch. 5 (ITM of smoke door assemblies) / NFPA 80 (2022)Trained inspector.
Prepare the OSHA 300A summarySafety & OSHA programAnnual29 CFR §1904.32Due before 1 February.
Lockout/tagout procedure reviewSafety & OSHA programAnnual29 CFR §1910.147(c)(6)Periodic inspection of energy control procedures.

Tier 2★ — qualified nationally, licensed locally

The honest middle. Under the national code a qualified person may perform these; in practice many states and AHJs require a licensed technician, and insurers sometimes require it independent of the code. NFPA 72 is the clearest example — it qualifies individuals, not firms, so trained facility personnel can perform the annual test under the standard, yet a great many jurisdictions require NICET certification for exactly that task. Do not assume either answer. Ask, get it in writing, and file it.

TaskSystemFrequencyCode (edition)What qualifies your person
Supervisory device testing (sprinkler-connected: tamper, pressure switches)Fire alarmQuarterlyNFPA 72 Table 14.4.3.2 (supervisory device testing) (2022)NFPA baseline allows a qualified person; many jurisdictions require a licensed technician — confirm with your AHJ.
Full system test — control equipment, initiating devices, notification, HVAC shutdownFire alarmAnnualNFPA 72 §14.4 (annual ITM) (2022)NFPA 72 qualifies individuals, not firms — trained facility personnel may perform under the national code, but state/local licensing frequently applies and many AHJs require NICET certification.
Waterflow alarm devices, supervisory devices, FDC conditionSprinkler systemQuarterlyNFPA 25 §5.3.3 / §13.7 (2023)NFPA baseline allows a qualified person; many jurisdictions require a licensed contractor — confirm with your AHJ.
Main drain test at each riser (backflow / PRV on sole supply)Sprinkler systemQuarterlyNFPA 25 §5.3.3 (main drain quarterly where sole supply passes through backflow preventer or PRV) (2023)Trained facility staff commonly perform; some jurisdictions require a licensed contractor.
Main drain test (all risers)Sprinkler systemAnnualNFPA 25 §13.2.5 (2023)Qualified staff under NFPA; licensing commonly required locally.
Annual assembly inspection & functional test (13 criteria)Fire doorsAnnualNFPA 80 §5.2.1 (annual, 13 criteria) (2022)NFPA 80 requires a 'qualified person' — trained in-house staff qualify under the national standard, but many jurisdictions and insurers expect a licensed fire-protection company.
EPSS thorough inspection (full power chain)Emergency generatorSemi-annualNFPA 110 §8.3.1 (2022)Qualified staff under NFPA; many contracts/AHJs use a technician.
Full system inspection / serviceHVACAnnualASHRAE/ACCA 180 §6 (2018)Several states layer licensed-contractor requirements on annual mechanical service — confirm locally (Layer 3).
Fire, smoke and combination damper operational test — one year after installation, then every 4 yearsFire / smoke dampersEvery 4 yearsNFPA 80 §19.4 / NFPA 105 Ch. 6 (2022)Qualified damper technician; hospitals may use the 6-year cycle where the CMS conditions are met.
Fire, smoke and combination damper operational test — one year after installation, then every 6 years (hospitals)Fire / smoke dampersEvery 6 yearsNFPA 80 §19.4 / NFPA 105 Ch. 6 (hospital 6-year interval) (2022)Damper testing contractor. Hospitals run a 6-year cycle rather than the 4-year cycle used for other occupancies.
Dry-pipe / pre-action full trip test with control valve wide openSprinkler systemEvery 3 yearsNFPA 25 §13.4.4.2.2 (3-year full trip) (2020)Licensed sprinkler contractor.
Fire water storage tank interior inspection (drained or by diver)Fire water storage tankEvery 5 yearsNFPA 25 §9.2.6 (interior inspection) (2020)Licensed contractor; interval extends where corrosion protection is present.
Smoke control / stair pressurisation operational test — dedicated systemsSmoke control / stair pressurisationSemi-annualNFPA 92 §8.4.2 (dedicated: semiannual) (2021)Special inspector or commissioning agent; non-dedicated systems test annually.
Fire drill — 1st shift (retain signed sheet)Fire drills (by shift)QuarterlyNFPA 101 §19.7.1 / CMS LSC (2012)Facility staff; one drill per shift per quarter.
Fire drill — 2nd shift (retain signed sheet)Fire drills (by shift)QuarterlyNFPA 101 §19.7.1 / CMS LSC (2012)Facility staff.
Fire drill — 3rd shift (retain signed sheet)Fire drills (by shift)QuarterlyNFPA 101 §19.7.1 / CMS LSC (2012)Third-shift drills may be announced but must still be documented.
Elopement / missing resident drillEmergency preparedness drillsQuarterlyIndustry practice (senior-living task library)All staff; document search protocol and time to locate.
Full-scale community-based exercise, or facility-based if unavailableEmergency preparedness drillsAnnual42 CFR §483.73(d)(2)Required by the CMS Emergency Preparedness Rule.
All-hazards risk assessment (HVA) — facility and community basedEmergency preparedness drillsAnnual42 CFR §483.73(a)(1)Drives the emergency plan; review and re-sign yearly.
Emergency preparedness plan review and updateEmergency preparedness drillsAnnual42 CFR §483.73(a)Whole program, not just the written plan.
Rail safety audit — full entrapment-zone measurementElectric beds & railsAnnualFDA Hospital Bed Safety Workgroup guidanceTrained staff or vendor.
Legionella water management plan reviewWater management (Legionella)AnnualASHRAE 188 / CMS QSO-17-30 (2018)Designated water management team.
Receptacle testing at patient bed locations — polarity, ground continuity, retention forceElectrical distributionAnnualNFPA 99 §6.3.3.2 (12-month interval applies to receptacles not listed hospital grade) (2021)Required in patient care spaces.
Post the OSHA 300A (1 February – 30 April)Safety & OSHA programAnnual29 CFR §1904.32(b)(6)Must remain posted three months.
Fire marshal inspection (schedule and close out findings)Safety & OSHA programAnnualLocal AHJAHJ visit; track corrective actions to closure.

Tier 3 — certified or licensed only

These are not recoverable, and you shouldn't try. They need a credential, calibrated equipment, or a filing a facility cannot self-perform — detector sensitivity testing needs a calibrated kit, backflow tests get filed with the water authority by a certified tester, hood cleaning needs a certified company, elevators run through a state or local certificate program.

TaskSystemFrequencyCode (edition)What qualifies your person
Smoke detector sensitivity test (calibrated equipment)Fire alarmEvery 2 yearsNFPA 72 §14.4.5 (sensitivity) (2022)Year 1, then every 2 years. Needs calibrated test kit and NICET-level tech.
Full inspection — heads, pipe, hangers, bracing, signage, spare headsSprinkler systemAnnualNFPA 25 §5.2 (2023)Licensed fire-protection contractor.
Internal pipe assessment (obstruction investigation)Sprinkler systemEvery 5 yearsNFPA 25 §14.2 (2023)Licensed contractor.
Sprinkler head sample test — standard-response heads (50 years, then every 10)Sprinkler systemEvery 50 yearsNFPA 25 §5.3.1 (2023)Lab testing of representative sample.
Fire pump full-flow test (churn, 100%, 150% rated)Fire pumpAnnualNFPA 25 §8.3.3 (2023)Licensed contractor with flow equipment.
Standpipe flow testStandpipesEvery 5 yearsNFPA 25 §6.3.1 (2023)Licensed contractor.
Annual maintenance examinationFire extinguishersAnnualNFPA 10 §7.3 (annual maintenance) (2022)Certified extinguisher service company; new service tag.
Internal examination (stored-pressure)Fire extinguishersEvery 6 yearsNFPA 10 §7.3.3 (2022)Certified service company; 6-year service collar.
Hydrostatic test — water, wet chemical, AFFF (5-year cycle)Fire extinguishersEvery 5 yearsNFPA 10 Table 8.3.1 (5-yr agents) (2022)Certified test facility. Interval 5 or 12 years depending on extinguisher type.
Load bank test at rated capacity (if monthly loading <30%)Emergency generatorAnnualNFPA 110 §8.4.2.4 (annual load bank) (2022)Contractor with load bank.
Full-load test, 4 continuous hours (Level 1 systems)Emergency generatorEvery 3 yearsNFPA 110 §8.4.9 (36-month 4-hour) (2022)Contractor; Level 1 EPSS every 36 months.
Hood & exhaust inspection/cleaning — solid fuelCommercial kitchen hoodMonthlyNFPA 96 §12.4 (2024 ed.; §11.4 pre-2024) (2024)Certified hood-cleaning company; cleaning certificate.
Hood & exhaust inspection/cleaning — high-volume (24-hr, charbroil, wok)Commercial kitchen hoodQuarterlyNFPA 96 §12.4 (2024 ed.) (2024)Certified hood-cleaning company; certificate.
Hood & exhaust inspection/cleaning — moderate-volumeCommercial kitchen hoodSemi-annualNFPA 96 §12.4 (2024 ed.) (2024)Certified company; certificate + deficiency report.
Hood & exhaust inspection/cleaning — low-volume (church, seasonal)Commercial kitchen hoodAnnualNFPA 96 §12.4 (2024 ed.) (2024)Certified company; certificate with photo documentation (2024 ed.).
Kitchen suppression system inspectionCommercial kitchen hoodSemi-annualNFPA 96 §11.2 / NFPA 17A (2024)Factory-authorized technician.
Periodic inspection & test → certificateElevator(s)AnnualASME A17.1 §8.11 (periodic) (2019)Licensed elevator inspector (state/local program); certificate posted.
Backflow preventer test by certified tester, filed with water authorityBackflow preventer(s)AnnualLocal cross-connection control (ASSE 5013 tester)Certified backflow tester; report filed with the water authority.
External / internal inspection per state boiler program — certificate postedBoilerAnnualState boiler law (jurisdiction-governed)State boiler inspector or authorized insurer; intervals & credentials set by state boiler law, not NFPA.
Medical gas system ITMMedical gasAnnualNFPA 99 (ITM interval & ASSE credential — verify)Medical gas systems require scheduled ITM under NFPA 99 by credentialed personnel (commonly ASSE 6030/6040) — confirm scope and interval with your medical gas verifier.

The rule that decides all of it: documentation

Whichever tier a task sits in, the record is the compliance. During a survey or an AHJ inspection, an inspection with no written record is treated as a missed inspection — the work effectively did not happen. A defensible record names the task, the date, the person and what qualified them, the result, any deficiency found, the corrective action, and the next due date. That is the standard the log sheets in the calendar builder are built to.

One more thing worth internalizing: under NFPA 25 the building owner owns the program, not the contractor — even when the work is delegated by lease. Hiring it out transfers the labor, never the responsibility.

Build your calendar

Enter your systems and last inspection dates — the tool tiers every task for you and totals what's eligible in-house.

  1. 1Address
  2. 2Facility
  3. 3Systems
  4. 4Details
  5. 5Dates
  6. 6Review
Facility address

Printed on every output — the calendar header and log sheets. You can skip it and add it later.

Free · No signup. Everything is computed on your device — nothing is uploaded.

Questions

Can facility staff legally perform fire safety inspections?

For a large share of tasks, yes — the national codes require a “qualified person,” defined by training rather than license, for monthly extinguisher checks, emergency lighting tests, sprinkler gauge and valve inspections, generator checks and load runs, and fire-door walks. State and local licensing can override this for specific tasks.

Does NFPA 72 require a NICET-certified technician?

NFPA 72 qualifies individuals, not firms, so trained facility personnel may perform ITM under the national code. But many states and AHJs require NICET certification for the annual test specifically — confirm with your fire marshal rather than assuming either way.

Which tasks truly require a licensed contractor?

Annual sprinkler inspection and fire pump flow tests, hood cleaning, extinguisher annual maintenance and hydrostatic testing, detector sensitivity testing, backflow testing, elevator certificates, and generator load-bank testing — these need credentials, calibrated equipment, or filings.

What does “qualified person” actually mean?

Documented training on the specific task, not a job title. The practical test: can you produce a record showing who did it, what training qualified them, when, and the result? If not, it doesn't count in an audit.

How much can a facility save doing this in-house?

It concentrates in the recurring weekly and monthly tasks, which are billed most often and are almost entirely staff-eligible. The builder totals the estimated contractor spend for eligible tasks and keeps starred, locally-variable tasks out of the headline figure.

Per-system schedules: NFPA 25 · NFPA 72 · NFPA 96 · NFPA 110 · NFPA 80 · NFPA 10

No staff to run the program? CompliMaint provides screened W-2 maintenance techs — documentation every visit →

National consensus-standard baselines (NFPA, ASME, ASHRAE) with the edition noted per item. Your state, local fire marshal, water authority, or accrediting body may require more frequent service or licensed personnel where a qualified person is shown. Starred items are the most common points of local difference — confirm them with your AHJ. General information, not legal or engineering advice.